Find your product
Technical specifications
DENSITY
Approximately 860 kg/m3 one month after application
ECOLOGICAL DATA
Free of fibers, silica and halogens
FIRE RESISTANCE
Up to EI 240 (EN 1366-3)
TESTED PENETRATION SEAL IN
Flexible walls: min. thickness 100 mm;
Rigid walls: min. thickness of 100 mm;
Rigid floors: min. thickness of 150 mm;
TESTED SERVICE PENETRATION
- PVC-U pipes up to Ø 200mm;
- PE pipes up to Ø 55mm;
- ABS pipes up to Ø 55mm;
- SAN+PVC pipes up to Ø 55mm;
- Copper pipes up to Ø93mm;
- Copper pipes up to Ø93mm + FEF / MW insulation;
- Steel pipes up to Ø194mm;
- Steel pipes up to Ø194mm + FEF insulation;
- Single cables up to Ø80mm;
- Cable bundles up to Ø 100mm;
- Cable trays up to 300x25mm;
- Perforated steel trays up to 500x60mm
*FEF: Flexible Elastomeric Foam
*MW: Mineral Wool
DURABILITY AND SERVICEABILITY
Type Y2: intended for use at temperature below 0°C, with no exposure to rain nor UV. Includes lower use categories. (EOTA TR 024:2009)
APPROVALS
CE Marked 0843–CPR–0277
ETA 15-0757
ETAG 026-2 (2011) according EN 1366-3 Penetration Seals
THERMAL CONDUCTIVITY λ W/(m•K)
< 0.3 W /m K
Contact us for more information about this product